EPRO MMS6823 Data Acquisition Module

EPRO MMS6823 Data Acquisition Module

Item Number: MMS6823
Brand: EPRO
Price: $1
Lead Time: In stock
Description:Data Acquisition Module
Payment: T/T
Shipping Port: XIAMEN
Send Inquiry
Description

 

 overview:

 

EPRO MMS6823

The EPRO MMS6823 Data Acquisition Module is a supporting product of the MMS6000 turbine generator vibration monitoring and protection system, produced by the German company EPRO. It communicates with TSI (MMS6000 series) modules via RS485 for data acquisition and related configurations.

Note:When using Emerson's new framework, the 6830 should be selected to replace the 6823 as the communication module. The 6830 has identical functionality to the 6823 and the 48-pin terminal definitions are exactly the same. The 6830 module is a 2U, 19-inch rack-mounted unit installed within the TSI cabinet.

 

For more information, please contact:
Email: sales18@htechplc.com
Whatsapp:+86 18059275924

 

 

 Fuctions & Features:

Physical connection: MMS6823 connects to MMS6000 series modules through 12 RS485 communication ports (ports 2 to 13), and each port supports up to 12 modules.

MMS6823 data type:

  • Dynamic signal: vibration waveform (acceleration/velocity/displacement) from bearing vibration and shaft vibration modules.

 

  • Static signal: slowly changing parameters such as shaft displacement, eccentricity, differential expansion, etc. (DC signal).

 

  • Speed ​​and key phase: frequency signal taken from the speed module, used for phase analysis and frequency multiplication tracking.
EPRO MMS6823 Data Acquisition Module

 Maintenance and troubleshooting:

 

  1. Daily maintenance

Check whether the 48-pin terminal wiring is loose (especially the power supply and RS485 signal line) to avoid communication interruption caused by poor contact.
Power light off: Check the power supply circuit or terminal wiring.
Communication light flashes abnormally: It may be RS485 bus conflict or module address duplication.

 

2.Troubleshooting

 

Fault PhenomenonPossible CausesSolutions
No vibration data acquisitionRS485 communication interruptionTest bus voltage, replace communication cables, or check terminal resistors
Remote desktop connection failureIP address conflict or firewall blockReconfigure IP address or unblock TCP port (e.g., 3389)
Abnormal fluctuations in sampled dataLoss of synchronization signal or poor groundingInspect key phase signal connections and optimize grounding system
Incorrect Modbus data readingIncorrect register address mappingVerify the configuration in daq6823a.xml file
 