Yokogawa SDV144-S63 Digital Input Module

Overview
Yokogawa SDV144-S63 is a digital input module for the Yokogawa ProSafe-RS Safety Instrumented System (SIS). The module can be installed in a Safety Node Unit or a Safety Control Unit and is used to receive field switch/contact signals. The module is classified as a safety-critical input module. The suffix code "S" indicates the standard type, "6" indicates the presence of a signal line interface adapter without explosion-proof capability, and "3" indicates compliance with the ISA G3 standard.
🚀Fuction & features
- Withstand voltage rating: When the SDV144-S63 is connected to the SED4D terminal board using a dedicated signal cable, the withstand voltage is 500 V AC (*5). If a MIL connector cable is used, the withstand voltage depends on the cable specifications.
- Field wiring diagnostics: When used with the SCB100 (open-circuit detection, normally closed signal) and the SCB110 (short-circuit detection, normally open signal), the SDV144-S63 enables channel-level open-circuit and short-circuit fault detection. To detect both open-circuit and short-circuit conditions simultaneously, the configuration requires a combination of "SCB100 connected in parallel + SCB110 connected in series."
- Channel restrictions: The number of available channels and power supply may be limited for SDV144-SC models (*3).

Specifications
|
Category |
Specification |
|
Model |
SDV144-S63 |
|
Number of Inputs |
16-channel, module isolation (*3) |
|
Input Signal |
No-voltage contact |
|
Input Current |
6 mA ±20% (24 V DC at 0 Ω input) |
|
Contact Rating |
24 V DC +20%/-10% (*4), ≥10 mA |
|
External Power Supply |
24 V DC +20%/-10% (3)(4) |
|
Max. Permissible Input Voltage |
30.0 V DC (instantaneous) |
|
Input Response Time |
≤40 ms |
|
Withstand Voltage (1)(2)(*5) |
2 kV AC (1 min) between input signals and system |
|
Current Consumption |
290 mA max (5 V DC) |
|
Weight |
≈0.36 kg (pressure clamp/MIL cable) |
|
External Connection |
Pressure clamp terminal |
Questions & Answers
💡 FAQ
Q: What is the brand?
A: Yokogawa
Q: In which industrial fields is the SDV144-S63 used?
A: Safety interlock circuits: Emergency stop pushbuttons, safety door switches, high-high/low-low level alarm contacts.
Fire and gas detection systems: Alarm outputs from flame detectors and gas detectors.
Equipment status monitoring: Pump running status and valve limit switches.
Q: What does the "S63" suffix represent? Are there other models?
A:The suffix represents a specific specification code. The SDV144 series has multiple sub-models, such as S1, S2, S3, and so on.
Q: What is the withstand voltage of the SDV144-S63 module?
A: The withstand voltage is not fixed and depends on the secondary-side voltage rating to ground of the field power supply and the connected cables:
- If the secondary-side voltage rating to ground of the field power supply is lower than the module's nominal value, the voltage rating of the power supply applies.
- When using the dedicated signal cable (AKB331), the withstand voltage between the input signal lines and the system is 500 V AC.
- When using MIL connector cables, the withstand voltage depends entirely on the electrical specifications of the selected cable and must be verified separately.
Q: What is the payment method?
A: T/T
Q: Why choose us?
A: We are the supplier for industrial automation spare parts,We speciaized in PLC DCS and TSl system modules and spare parts for 10 years, With our professional expertise and extensive experience, we are well-equipped to meet your requirements.
Contact us
Our address
Room 1904, Building B, Diamond Coast, No. 96 Lujiang Road, Siming District, Xiamen, Fujian, China
Phone Number
+86 18059275924
sales18@htechplc.com

Hot Tags: yokogawa sdv144-s63 digital input module, yokogawa sdv144-s63 digital input module manufacturers, suppliers