overview:
ABB SPAJ140C-CA overcurrent and fault relay is mainly used for selective short circuit and ground fault protection of radial feeders in solid, resistance or impedance grounded power systems. It is a secondary relay connected to the current transformer of the protected object, detects faults by monitoring phase and neutral currents, and starts, trips circuit breakers, initiates automatic reclosing, sounds alarms, and records fault data according to the configured functions. The relay can also be used in other application scenarios that require single-phase, two-phase or three-phase overcurrent protection and non-directional ground fault protection, and has circuit breaker failure protection function.

Fuctions & Features:
- Overcurrent protection functions:
- Three-phase low-set phase overcurrent units with definite time or inverse minimum time (IDMT) characteristics.
- Three-phase high-set phase overcurrent units with instantaneous or definite time functions.
- Ground fault protection functions:
- Low-set, non-directional ground fault units with definite time or inverse minimum time (IDMT) characteristics.
- High-set, non-directional ground fault units with instantaneous or definite time functions.
- Various inverse time curves: When the IDMT characteristic is selected, there are six time/current curves to choose from for the low-set stage of the overcurrent unit and ground fault unit.

Specification:
|
Category |
Details |
|
Output contact ratings - Tripping contacts |
|
|
Terminals |
65 - 66, 74 - 75 |
|
Rated voltage |
250 V dc/ac |
|
Continuous carry |
5 A |
|
Make and carry for 0.5 s |
30 A |
|
Make and carry for 3.0 s |
15 A |
|
Breaking capacity for dc, when the trip circuit time - constant L/R ≤ 40 ms, at 48/110/220 V dc |
5 A/3 A/1 A |
|
Output contact ratings - Signalling contacts |
|
|
Terminals |
70 - 71 - 72, 68 - 69, 77 - 78, 80 - 81 |
|
Rated voltage |
250 V dc/ac |
|
Continuous carry |
5 A |
|
Make and carry for 0.5 s |
10 A |
|
Make and carry for 3.0 s |
8 A |
|
Breaking capacity for dc, when the signal circuit time - constant L/R ≤ 40 ms, at 48/110/220 V dc signal circuit voltage |
1 A/0.25 A/0.15 A |
|
External control inputs |
|
|
Blocking, remote reset or remote setting input |
10 - 11 |
|
Control voltage level |
18...265 V dc or 80...265 V ac |
|
Control current of activated input |
2...20 mA |
- Questions and Answers:
Q: What is the brand?
A:
Q: What is the type?
A:
Q: What is the warranty period?
A: 1 year.
Q: What is the delivery time?
A:in stock
Q: Where is the shipping location?
A: Xiamen.
Q: What is the payment method?
Answer: T/T (Telegraphic Transfer).
Contact us to get a quick quote!
If you are interested in this product or need more technical details, please contact us immediately! Our professional team will provide you with detailed product information and competitive quotations to ensure that you get the most suitable solution at the best price.
📞 Whatsapp/Wechat/Mobile: +86 18059275924
📧 Email: sales18@htechplc.com
Hot Tags: abb spaj140c-ca overcurrent and earth-fault relay, abb spaj140c-ca overcurrent and earth-fault relay manufacturers, suppliers, Modicon AS B872 100, ABB IMMFP02, ABB IEMMU21 Module Mounting Unit, EPRO PR9376 010 001 Hall Effect Speed Proximity Sensor, 1747-L551, Allen Bradley 1794 ACNR15