Overview:

ABB IOR810 Gateway Module (For HN800)
ABB IOR810 is a S800 I/O gateway module for the HN800. This module primarily connects the Symphony Plus SD series and HR series controllers to the S800 I/O modules. the module scans and manages the data of the S800 I/O modules, then transmits these input/output signals through the HN800 bus to the higher-level Symphony Plus controller for processing. ABB IOR810 provides an expansion capability for existing Symphony Plus or Symphony Harmony control systems and serves as an interface device between large DCS controllers and distributed I/O.
Function & Features:

- Multiple I/O Types:The ABB IOR810 supports various signal modules within the S800 I/O subsystem, including basic AI/AO, DI (contact input), SOE DI, DO, pulse input, temperature device inputs (RTDs and thermocouples), as well as intrinsically safe and redundant I/O modules.
- Long-Distance Communication:Through a fiber-optic bus and repeaters, the ABB IOR810 enables long-distance communication of up to 3,000 meters between the controller and the modules.
- Large-Scale I/O Expansion:A single ABB IOR810 module can connect up to 7 cluster modems, supporting as many as 84 S800 I/O modules.
Specifications:
| Parameter | Details |
|---|---|
| Product Model | IOR810 |
| Associated System | 800xA S800 I/O |
| Upstream Interface (to Controller) | HN800 Bus |
| Downstream Interface (to I/O) | Fiber Optic Modulebus |
| Modulebus Fiber Distance |
1. Plastic Optical Fiber (POF): 15m 2. HCS Fiber: 200m 3. Glass Fiber (with TB825 converter): 1000m |
| Width | 43.6mm |
| Height | 124 mm |
| Depth | 109 mm |
| Net Weight of IOR810 | 0.42kg |
Questions & Answers
💡 FAQ
Q: How to troubleshoot when the ABB IOR810 module status indicators are off or show errors?
A:Basic troubleshooting steps:
- Check power supply:Verify that the HBX01L/R is correctly installed and that the power supply is functioning properly.
- Check bus connections:Ensure that the HN800 electrical or fiber-optic links are securely connected, the terminator (TER800) is installed correctly, and the fiber attenuation is within the allowable range.
- Check downstream links:Confirm that the Modulebus fiber connections from the IOR810 to each cluster modem are normal.
- Check configuration:Verify that the controller configuration has been correctly downloaded, and that the IOR810 is properly defined and enabled in the configuration.
Q: How many S800 I/O points can one IOR810 support at most?
A: The physical limits of the IOR810 are:
- A maximum of 7 cluster modems can be connected.
- Each cluster modem can support up to 12 I/O modules.
- Therefore, the IOR810 can manage a maximum of 7 × 12 = 84 S800 I/O modules.
- The total number of I/O points depends on the channel count of each module (for example, 8-channel DI modules, 4-channel AI modules, etc.).
Q: Can the IOR810 operate independently?
A:No, it cannot.The IOR810 must be used together with the HBX01L and HBX01R bus extenders. The HBX01 units provide the HN800 bus interface and the operating power for the module. Without them, the IOR810 cannot connect to the controller network or function properly.
Q: What is the return and exchange policy?
A: Returns or exchanges are accepted within 7 days of receiving the goods if there are any quality issues, excluding damage caused by human error or misuse.
Q:What are the available shipping methods?
A: FedEx, DHL, UPS, and others.
Contact us
Our address
Room 1904, Building B, Diamond Coast, No. 96 Lujiang Road, Siming District, Xiamen, Fujian, China
Phone Number
+86 18059275924
sales18@htechplc.com


why choose us?
We specialize in providing industrial automation and control solutions, including ABB, GE, Bently Nevada, and other critical DCS/PLC components. Here's why customers trust us for their industrial automation needs:
one-stop solution
professional team
Quality Assurance
After-sales service




Our Partners








Hot Tags: abb ior810 gateway module for hn800, abb ior810 gateway module for hn800 manufacturers, suppliers, ABB AI845 3BSE023675R1 Analog Input S R HART 8 Ch, ABB AO820 AO820 EA 3BSE008546R1 Analog Output 4 Ch Module, ABB CI801 CI801 EA 3BSE022366R1 PROFIBUS FCI S800 Interface, ABB PM856K01 3BSE018104R1 Processor Unit Kit, ABB PM866K01 3BSE050198R1 Processor Unit Kit, ABB TB805 3BSE008534R1 Bus Outlet