overview:
ABB CI540 I/O Bus Extension Module works as an I/O bus extension unit for ABB AC800M control systems, handling signal transmission between the controller and remote I/O stations. It extends the AF100 I/O bus and separates local bus segments from remote branches to manage bus load on the DCS network. This ABB CI540 module supports signal forwarding over longer distances when the standard AF100 bus length cannot cover field I/O locations.


Fuctions & Features:
- AF100 I/O bus extension for AC800M controllers
- Supports segmentation of the main bus to reduce signal interference
- Status LED indicators for power and bus communication status
- DIN rail mounting inside standard control cabinets
- Works with S800 remote I/O clusters
- Supports hot swapping in qualified system configurations
- Built-in bus termination function for end-of-line setup
- Simple wiring layout with detachable terminal blocks
Specification:
| Parameter | Details |
|---|---|
| Part Number | CI540 |
| Brand | ABB |
| Product Type | I/O Bus Extension Module |
| Supported Bus Protocol | AF100 |
| Compatible Controller Series | AC800M |
| Supply Voltage | 24 VDC |
| Operating Voltage Range | 19.2 VDC to 30 VDC |
| Rated Current | 180 mA |
| Power Consumption | 4.3 W max |
| Bus Communication Rate | 1.5 Mbps |
| Maximum Extension Distance | 1000 m at 1.5 Mbps |
| Max I/O Stations per Extended Segment | 32 |
| Operating Temperature Range | 0 °C to +60 °C |
| Storage Temperature Range | -40 °C to +85 °C |
| Relative Humidity | 5 % to 95 %, non-condensing |
| Protection Class | IP20 |
| Mounting Type | DIN 35 mm rail |
| Module Dimensions | 100 mm × 75 mm × 22 mm |
| Net Weight | 160 g |
| Number of Status LEDs | 3 |
| Terminal Count | 8 screw terminals |
| Certification | CE, RoHS |
Model Comparison
| Model | Bus Type | Max Extension Distance | Supported Controller | Main Difference |
|---|---|---|---|---|
| CI540 | AF100 | 1000 m | AC800M | Standard AF100 bus extender, most common replacement unit |
| CI541 | AF100 | 500 m | AC800M | Compact version, lower station capacity |
| CI542 | AF100 + optical | 2000 m (fiber) | AC800M | Optical fiber bus extension for high-noise environments |
ABB CI540 - Q&a
Q: Can the ABB CI540 module run with PM866 controller?
A: Yes, CI540 works with PM866 when the AC800M firmware version meets the requirement for AF100 bus hardware.
Q: Does ABB CI540 support fiber optic connection?
A: No. CI540 uses copper AF100 bus. Choose CI542 if fiber transmission is required.
Q: Is hot swap allowed for this I/O bus extension module?
A: Hot swap can be performed while the controller remains online if the system is configured properly.
Q: Can CI540 connect directly to S900 I/O modules?
A: No. CI540 is built for S800 I/O stations. It cannot communicate with S900 I/O hardware..